- Contact Person : Mr. Su Shanxiu
- Company Name : Zhengzhou Sutong Electric Equipment Co., Ltd.
- Tel : 86-371-86178593
- Fax : 86-371-86178593
- Address : Henan,Zhengzhou,No.197, hanghai M. Road
- Country/Region : China
- Zip : 450015
XGN2-12 12Kv electrical cubicle type switchgear
We offer OEM service for you!
XGN2-12 12Kv electrical cubicle type switchgear1.Rated voltage:3.6~12KV
2:Rated Current:630~3150A
3.AC 3 phase 50Hz
1.Descriptions and applications:
XGN2-12 Box type Metal-enclosed Switchgear(i.e. switch cabinet),is used for accepting and distributing electric energy in the power system with rated voltage of 3.6-12KV,three phase AC,50Hz and rated current of 630-3150A.It's particularly suitable for frequent operation occasion.
2.Operating environment:
1.Ambient temperature:-10°C-+40°C;
2.Seismic intensity:≤ magnitude 8;
3.Altitude:≤1000Meter(if≥1000M,technical department will design specially);
4.Relative humidity:daily mean≤95%,Monthly mean≤90%;
5. Places have no fire,no explosion danger, no serious pollution,no chemical corrosion and no violent vibration.
3.Product Model and Implication:
4.Main Technical specifications:
No. | Items | Unit | Technical datas | |||||
1 | Rated voltage | KV | 3.6 | 7.2 | 12 | |||
2 | Rated current | A | 630 | 1000 | 1250 | 2000 | 2500 | 3150 |
3 | Rated short circuit breaking current | KA | 20 | 31.5 | 40 | |||
4 | Rated short-time withstand current | KA | 20 | 31.5 | 40 | |||
5 | Rated peak withstand current | KA | 50 | 80 | 100 | |||
6 | Rated short circuit making current | KA | 50 | 80 | 100 | |||
7 | Duration Time of short-time withstand current | S | 4 | |||||
8 | Protection Class | IP2X | ||||||
9 | Busbar system | single busbar,main and transfer busbar system,double busbars | ||||||
10 | Operating mode | electromagnetic type,spring energy saving type | ||||||
11 | Overall dimensions(Width×Depth×Height) | mm | 1100*1200*2650(below 1250A) | |||||
12 | Weight | Kg | 1000 |
6.Structure:
7.Overall and mounting dimensions (mm) :
height B | 2300(2200) | |
Width A | Rated current of the branch busbar is ≤1250A, thermal stable current is 40ka | 800(650) |
Rated current of the branch busbar is ≥1600A | 1000 | |
Depth C | Cable in-out line | 1500 |
Arial in-out line | 1660 |
Width A | Height B | L1 | L2 | L3 | L4 |
800 | 1500 Cable | 530 | 630 | 150 | 490 |
1660 Aerial | 530 | 630 | 310 | 650 | |
1000 | 1500 Cable | 730 | 830 | 150 | 490 |
1660 Aerial | 730 | 830 | 310 | 650 |
XGN2-12 12Kv electrical cubicle type switchgear